Troubleshooting Controller
- To test the controller's output, connect a solenoid to one of the controller's red and white wire pairs. Institute a test run via the handset with 1 minute on the station in question and zero minutes on the other station. If the solenoid is not installed, verify that the plunger retracts and extends or that you hear the sound of the plunger latching. If the solenoid is installed onto a valve, see that the valve turns on and the sprinklers or drip system is working. If it does not turn on, the plunger does not retract and extend or no sound is heard of the plunger latching, repeat the process using a second solenoid. If the problem continues you may have an issue with the controller wires and the waterproof connectors.
- The LEIT-2 controllers will only function with S-305DC solenoid or 305DCXXX valve
- The LEIT-2 controllers will only function with compatible sensors (HUNTER MINI-CLICK or RAIN BIRD RSD)